NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-00-733-4565 Item Description: Circuit Breaker | 5925 | 007334565 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | |||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
Xm633600 | 2 | 9 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
ABHP | OVERALL LENGTH | 24.523 INCHES NOMINAL |
ABKW | OVERALL HEIGHT | 5.420 INCHES NOMINAL |
ABMK | OVERALL WIDTH | 8.250 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AKPX | POLE QUANTITY | 3 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 4 UNTHREADED HOLE |
BBRJ | SPECIAL HANDLING FEATURE | MAGNETIC |
CBBL | FEATURES PROVIDED | ADJUSTABLE TRIP RELEASE AND CURRENT LIMITER |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 480.0 AC ALL LOCATIONS |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 100000.0 AC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL-MAGNETIC ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS ALL LOCATIONS AND TIME DELAY ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE TWO |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 20.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 32.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | GENERAL PURPOSE |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 40.0 DEG CELSIUS NOMINAL ALL LOCATIONS |
FREQ | FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
PKWT | UNPACKAGED UNIT WEIGHT | 58.000 POUNDS |
TTQY | TERMINAL TYPE AND QUANTITY | 6 COMPRESSION |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.250 INCHES NOMINAL |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 600.0 AMPERES AC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPSF | ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | +3000.0/+6000.0 AC ALL LOCATIONS |